DL/T 1592-2016 in English
VALIDTechnical specificaon of electrical energy data acquision terminal test equipment
- Issued on:2016-08-16
- Implemented on:2016-12-01
- File Format:PDF
- Delivery:Via email within 1~3 business days
$301.00
| Standard No: | DL/T 1592-2016 |
| Document status: | VALID |
| Title in English: | Technical specificaon of electrical energy data acquision terminal test equipment |
| Title in Chinese: | 电能信息采集终端检测装置技术规范 |
| Language: | English |
| File Format: | Electronic (PDF) |
| Delivery: | Via email within 1~3 business days |
| Issued on: | 2016-08-16 |
| Implemented on: | 2016-12-01 |
| Professional Classification: | DL-Electricity |
| Related Keywords: | terminal test equipment introduction standard background
key test methods insulation strength test test methods power consumption test average test time |
| Related Topics: | dl/t 1592-2016
dl/t1592-2016 dl/t1592 Quality Information Collection Technology Collection terminal terminal detection Hydropower project information collection Digital information collection module and control device Meteorological inspection and collection technology Water conservancy collection terminal technology Information collection specification requirements Collection terminal detection ny/t 1592 |
Introduction
Standard Background and Scope of Application
This standard was issued by the National Energy Administration in 2016 and specifies the technical requirements and test methods for electric energy information collection terminal detection devices. It is applicable to the acceptance of detection equipment for various types of collection terminals such as special transformer terminals, public transformer terminals, and plant and station terminals, and provides a technical basis for the quality control of electric energy metering equipment in the power industry.
Analysis of core technical requirements
| Technical indicators | Parameter requirements | Test basis |
|---|---|---|
| Power source output | Voltage 0-120% adjustable, fineness 100mV | JJG597-2005 |
| Standard table accuracy | Meets 0.05 level requirements | JG597-2005 |
| Communication protocol | Supports 7 protocols including DL/T698.41 | Appendix A |
| MTBF | ≥20,000 hours | 5.4.1.1 |
Typical application case
After a provincial power grid company adopted the detection device that complies with this standard, the terminal acceptance qualification rate increased from 92% to 99.6%, and the average test time was shortened by 40%.
Key test methods
- Insulation strength test: 2kV power frequency withstand voltage for 1min, leakage current ≤5mA
- Communication protocol compatibility test: 100% pass rate required
- Power consumption test: ≤5kVA (measured by 1.0-level meter)
Implementation suggestions
Purchasing precautions
- Verify whether the detection device has multi-protocol compatibility
- Check the power source harmonic output function (2-21 times)
- A complete command word interface protocol is required (Appendix A)
Main points for use and maintenance
- Regularly calibrate the standard meter (recommended cycle is 6 months)
- Maintain the ambient temperature at 15-30℃ and the humidity at 10-75%
- Establish a test plan management system (Standard 5.4.2.1)

Loading PDF document...
Error loading PDF. Please make sure the file is valid and try again.
We also recommend
-

DL/T 790.12-2001 in English
Distribution Automation Using Distribution Line Carrier Part 1: General Provisions Part 2: Guidelines for Formulation of Specifications
2001-12-26 -

DL/T 1107-2019 in English
Basic specifications of automatic components for hydraulic power plants
2019-06-04 -

DL/T 790.11-2001 in English
Distribution Automation Using Distribution Line Carriers Part 1: General Part 1: Architecture of Distribution Automation Systems
2001-12-26 -

DL/T 646-1998 in English
Technical specification of manufacturing steel transmission pole structures
1998-03-19