DL/T 2002-2019 in English
VALIDOperation specification for converter transformer
- Issued on:2019-06-04
- Implemented on:2019-10-01
- File Format:PDF
- Delivery:Via email within 1~3 business days
$253.00
Introduction
Analysis of the core content of the standard
| Technical dimension | DL/T 2002-2019 requirements | Comparison of conventional transformer standards |
|---|---|---|
| Protection configuration | Mandatory requirement for three-out-of-two tripping logic and shock-proof gas relay | Conventional dual configuration is sufficient |
| Cooling system | Dual independent power supplies + forced input function + group delay control | Mainly single power supply system |
| Short-circuit tolerance | Need to match the actual short-circuit capacity of the system | According to GB1094.5 standard value |
Detailed explanation of key technical requirements
4.1 Special provisions for protection devices
Article 4.1.6 of the standard clearly states: When on-load tap changers are operated in parallel, each switch needs to be independently equipped with an oil flow relay, and the installation slope is 1%-3%. Typical case: A ±800kV converter station failed to meet the slope requirements, resulting in protection malfunction, and the operation was stable after adjustment.
Analysis of standard evolution
Main changes compared to the 2018 version:
- Added installation specifications for fast-acting oil pressure relays (Article 6.3.2)
- Detailed requirements for detection of aging of silicone rubber for bushings (Article 6.5.1)
- Supplementary earthquake prevention measures for earthquakes with an intensity of seven or above (Article 4.5.6)
Implementation suggestions
- Operation and maintenance strategy: It is recommended to establish a special inspection list for commutator transformers, with a focus on checking the hydrophobicity of silicone rubber for bushings (every quarter)
- Technical transformation: For tap changers that have been in operation for more than 7 years, hoisting inspections shall be carried out in accordance with the requirements of Article 9.2
- Data management: Improve the non-electrical protection action record database and establish a fault analysis model in accordance with Article 7.2

Loading PDF document...
Error loading PDF. Please make sure the file is valid and try again.
We also recommend
-

DL/T 790.12-2001 in English
Distribution Automation Using Distribution Line Carrier Part 1: General Provisions Part 2: Guidelines for Formulation of Specifications
2001-12-26 -

DL/T 790.11-2001 in English
Distribution Automation Using Distribution Line Carriers Part 1: General Part 1: Architecture of Distribution Automation Systems
2001-12-26 -

DL/T 1114-2009 in English
Steel-work corrosion and protectection-test methods for thermal spraying(Zinc、aluminium and their alloys)
2009-07-01