Sign In |Help & Support
ALL SECTORS
  • ALL SECTORS
  • GB(National Standard)
  • CB(Shipping)
  • CECS(Engineering Construction)
  • CJ(Urban Construction)
  • CY(News and Publication)
  • DB(Provincial Standard)
  • DL(Electricity & Power)
  • DZ(Geology & Mineralogy)
  • FZ(Spinning & Textile)
  • GA(Public Security)
  • HB(Aviation)
  • HG(Chemical Industry)
  • HJ(Environmental Protection)
  • JB(Machinery)
  • JC(Building Materials)
  • JG(Building & Construction)
  • JJ(Metering)
  • JT(Highway & Transportation)
  • LY(Forestry)
  • MT(Coal)
  • NB(Energy)
  • NY(Agriculture)
  • QB(Light Industry)
  • QC(Automobile & Vehicle)
  • QJ(Aerospace)
  • SH(Petrochemical)
  • SJ(Electronics)
  • SL(Water Resources)
  • SN(Commodity Inspection)
  • SY(Oil & Gas)
  • TB(Railway & Train)
  • YB(Ferrous Metallurgy)
  • YC(Tobacco)
  • YD(Telecommunication)
  • YY(Medical Device)
Database: 365,228(8 Aug 2026)
gas-insulated bushings oil-impregnated paper bushings glue-impregnated paper bushings technical specification bushings coriolis force insulation roller beds technology assessment indicator system
GB/T 24840-2018 in English

GB/T 24840-2018 in English

VALID

Technical specification for bushings of 1 000 kV AC system

  • Issued on:2018-07-13
  • Implemented on:2019-02-01
  • File Format:PDF
  • Delivery:Via email within 5 business days
Price(USD): $310.00
$301.00
Standard No: GB/T 24840-2018
Document status: VALID
Title in English: Technical specification for bushings of 1 000 kV AC system
Title in Chinese: 1000kV交流系统用套管技术规范
Language: English
File Format: Electronic (PDF)
Delivery: Via email within 5 business days
Issued on: 2018-07-13
Implemented on: 2019-02-01
Superseding: GB/Z 24840-2009 Technical specification for bushing of 1000 kV AC system
ICS Classification: 29.240.01-Power transmission and distribution networks in general
Chinese Classification: K40-Electric transmission and transformation equipment in general
Professional Classification: GB-National Standard
Related Keywords: gas-insulated bushings
oil-impregnated paper bushings
glue-impregnated paper bushings
technical specification
bushings
Related Topics: Technical Measurement Exchange Group
Test Technology Exchange Group
flow system
GBT24840
GB/T 24840-2018

《GB/T 24840-20181000kV交流系统用套管技术规范》由524(中国电力企业联合会)归口,TC569(全国特高压交流输电标准化技术委员会)执行,主管部门为中国电力企业联合会。


Introduction

Standard Technology Evolution and Background

As the technical specification for key UHV AC transmission equipment, this standard reflects my country's technological accumulation in the field of 1000kV bushings. Compared with the 2009 version, the main technical upgrades include:

Improvement dimensions2009 version2018 versionTechnical significance
Seismic parametersSingle fortification standardFortification for 6/7/8 degreesImprove reliability in earthquake-prone areas
Power frequency tolerance time1min5minStrengthen long-term operation stability
Partial discharge measurement1.05Um/√31.1Um/√3Detection sensitivity increased by 30%

Analysis of core performance indicators

Insulation performance requirements

The standard specifies differentiated indicators for three types of bushings:

  • Oil-impregnated paper bushings: tanδ≤0.4% (20℃)
  • Glue-impregnated paper bushings: tanδ≤0.7%
  • Gas-insulated bushings: tanδ limit cancelled

Mechanical performance parameters

Cantilever load is divided into two levels:

Current range (A)Load I (N)Load II (N)
800-160031505000
2000-315050008000

Key test methods

Type test process

  1. Lightning impulse test: positive/negative polarity 15 times each
  2. Long-term power frequency test: 1100kV for 5min
  3. Thermal stability test: △tanδ≤0.02%/h

Partial discharge detection

Three-stage voltage method is used:

Insulation type1.1Um/√3(pC)
Oil impregnated paper≤5
Glue impregnated paper≤5

Implementation suggestions

Selection considerations

  • Areas with seismic intensity ≥7 degrees should use horizontal acceleration 0.3g design
  • Composite bushing is preferred in heavily polluted environments
  • Oil-SF6 bushing requires double sealing verification

Operation and maintenance management points

The on-site handover test must include:

  1. Main insulation tanδ measurement (10kV)
  2. SF6 gas micro-water test (≤250μL/L)
  3. Sealing inspection (annual leakage rate <0.5%)