Analysis of the core content of the standard
This standard specifies the technical requirements for pressure regulating devices for gas combustion equipment. It is applicable to pressure regulators with a nominal size of ≤DN250 and a maximum inlet pressure of ≤500kPa, covering self-operated pressure regulators and devices with auxiliary energy.
| Regulator classification | Pressure stabilization capability requirements | Applicable gas types |
|---|---|---|
| Grade A | ±15% or ±0.1kPa | Artificial gas/natural gas/liquefied petroleum gas |
| Grade B | +15% -20% |
Key technical requirements
Structural safety design
- The breathing hole must meet the anti-blocking requirements, with a diameter ≥5mm
- Adjustable devices must be equipped with tamper-proof sealing measures
- Withstand pressure ≥ 1.15 times the maximum working pressure
Material specifications
Typical case: A certain model of spring-type pressure regulator uses SUS304 stainless steel diaphragm and performs 30% better than the industry average in the salt spray test
Performance test system
Key test items
- Air tightness test: ≤0.07L/h leakage
- Overpressure capability test: 400kPa pressure for 3 minutes
- Durability test: 50,000 opening and closing cycles
Implementation suggestions
Manufacturers should establish a three-level inspection system: Raw material entry inspection → process inspection → factory full inspection, focusing on monitoring the fatigue strength of the diaphragm and the sealing of the valve seat.
Standard Evolution Analysis
Compared with ISO23551-2:2018, this standard has the following major improvements:
- Added EP overpressure capability indicator
- Refined the applicable scope of DC power supply
- Strengthened vibration test requirements (10-150Hz)

Loading PDF document...
Error loading PDF. Please make sure the file is valid and try again.
We also recommend
-

GB/T 45385-2025 in English
Safety and control devices for gas burners and gas-burning appliances—Particular requirements—Vent valves
2025-03-28 -

GB/T 37992-2019 in English
Safety and control devices for gas burners and gas-burning-appliances—Particular requirements—Value-proving systems for automatic shut-off valves
2019-08-30 -

GB/T 31911-2015 in English
Methods for determination of emissions from appliances burning gaseous fuels
2015-09-11 -

GB/T 16411-2023 in English
Universal test methods of gas burning appliances for domestic use
2023-08-06 -

GB/T 41320-2022 in English
Non-household gas-fired space heater
2022-03-09