DL/T 1986-2019 in English
VALIDTechnical specification for gas detecting in SF6 gas mixture insulated equipment
- Issued on:2019-06-04
- Implemented on:2019-10-01
- File Format:PDF
- Delivery:Via email within 1~3 business days
$185.00
Introduction
Analysis of the core content of the standard
This standard establishes for the first time the detection technology system for sulfur hexafluoride mixed gas insulation equipment, and standardizes the technical requirements for 10 major categories of detection items for mixed gases such as SF6/CF4 and SF6/N2.
Comparison of key detection indicators
| Detection items | Periodic requirements | Main methods | Accuracy requirements |
|---|---|---|---|
| Mixed gas ratio | 1 time/year | Gas chromatography/sensor method | ±0.5% |
| Humidity | According to DL/T 506 | Condensation dew point method | ±1℃ |
| Decomposition products | When necessary | Electrochemical method | 0.1μL/L |
Technical Innovation Points
1. Infrared imaging leak detection technology: For the first time, the technical requirement of NETD (noise equivalent temperature difference) ≤ 0.05K is clarified, and the visual detection of SF6 leaks with a 10-second response is realized.
2. Dual sensor combination: The mixed gas ratio detection uses a thermal conductivity/infrared sensor and an electrochemical oxygen sensor to work together to ensure that the SF6 detection error is ≤ 1% and the O2 detection error is ≤ 0.1%.
Typical application cases
Case 1: Abnormal gas mixture ratio of GIS equipment
A 500kV substation uses SF6/N2(30/70) mixed gas. Gas chromatography detection found that the N2 content deviation reached 3.2%. After investigation, it was found that the charging ratio control valve was faulty.
Case 2: Decomposition product warning
The DL/T 1205 method detected that the SO2+H2S content exceeded the limit value (2μL/L), and the internal arc discharge defect of the circuit breaker was discovered in time.
Implementation Suggestions
1. Testing equipment selection: Prioritize multi-parameter detectors that meet the requirements of Article 6.1.1.2 of the standard, which must have annual calibration functions.
2. Tail gas treatment: Strictly implement the requirements of Article 7.5, and use alkaline solution absorption or special recovery equipment to treat the test tail gas.
3. Data recording: The test report should contain 9 core contents as required by Chapter 8, especially environmental parameters and instrument calibration information.