Introduction
Core requirements for the construction of carbon fiber composite core conductors
According to the revised 2019 version of the standard, the construction of carbon fiber composite core conductors (models such as JLZ2X1/F2A-1660/95) requires attention to the following key parameters: tension control shall not exceed 20%RTS, pulley envelope angle ≤25°, line section length 6-8km (soft aluminum type shall not exceed 6km), etc.
Comparison of new and old standards
| Technical indicators | DL/T 5284-2012 | DL/T 5284-2019 | Revision points |
|---|---|---|---|
| Paying-off tension | Not clearly specified | ≤20%RTS | New mandatory requirements |
| Construction machinery and tools | General equipment | Special assembled tractor | Add anti-shrinkage core design |
| Crimp inspection | Maximum distance to edge | Increase the minimum allowable value (0.86D-0.2mm) | Prevent overvoltage damage |
Detailed explanation of key construction processes
1. Tension pay-off control
For conductors below 710mm², the tension machine drum diameter must be ≥50 times the conductor diameter; for conductors 1660mm², it must be ≥2200mm. The bottom diameter of the wire-laying pulley groove should meet the following requirements:
- Conventional conductor: ≥30 times the diameter
- Large-section conductor: ≥1500mm
2. Crimping technical specifications
- The distance between the edges is controlled at (0.86D±0.2)mm
- The curvature of the connecting tube is ≤1% of the tube length
- The curvature of the crimping area of the tension clamp is ≤2%
Typical problem case: Due to the use of non-special pressing molds in a certain project, the ovality of the crimping tube exceeded the standard and needed to be sawed off and re-pressed.
Construction quality assurance measures
| Links | Key control points | Inspection methods |
|---|---|---|
| Core rod connection | Wedge clamp preload inspection | Vernier caliper measurement of l3/l4 dimensions |
| Aluminum tube crimping | Even application of power grease | Three-way distance detection |
| Accessory installation | Wire lifter envelope angle ≤25° | On-site measurement with an inclinometer |

Loading PDF document...
Error loading PDF. Please make sure the file is valid and try again.
We also recommend
-

DL/T 790.12-2001 in English
Distribution Automation Using Distribution Line Carrier Part 1: General Provisions Part 2: Guidelines for Formulation of Specifications
2001-12-26 -

DL/T 790.11-2001 in English
Distribution Automation Using Distribution Line Carriers Part 1: General Part 1: Architecture of Distribution Automation Systems
2001-12-26 -

DL/T 5385-2020 in English
Code for construction supervisionof dam safety monitoring system
2020-10-23 -

DL/T 646-1998 in English
Technical specification of manufacturing steel transmission pole structures
1998-03-19