DL/T 802.2-2017 in English
VALIDTechnical requirements for electric cable conduits.Part 2:Cable conduits of fiberglass reinforced plastics
- Issued on:2017-08-02
- Implemented on:2017-12-01
- File Format:PDF
- Delivery:Via email within 1~3 business days
$271.00
| Standard No: | DL/T 802.2-2017 |
| Document status: | VALID |
| Title in English: | Technical requirements for electric cable conduits.Part 2:Cable conduits of fiberglass reinforced plastics |
| Title in Chinese: | 电力电缆用导管 第2部分:玻璃纤维增强塑料电缆导管 |
| Language: | English |
| File Format: | Electronic (PDF) |
| Delivery: | Via email within 1~3 business days |
| Issued on: | 2017-08-02 |
| Implemented on: | 2017-12-01 |
| ICS Classification: | 29.060.20-Cables |
| Chinese Classification: | K13-Cable and its accessory |
| Professional Classification: | DL-Electricity |
| Related Keywords: | key technical requirements
technical requirements standard revision technical elements electric cable conduits.part cable conduits |
Introduction
Core changes in the standard revision
| Technical elements | 2007 edition | 2017 edition | Description of changes |
|---|---|---|---|
| Reinforcement materials | No clear restrictions | Mandatory use of alkali-free glass fiber (alkali metal oxide ≤0.8%) | Prohibition of high/medium alkali glass fiber to improve corrosion resistance |
| Process type | Mechanical winding only | New BWFRP braided winding pultrusion process | Expanded production process diversity |
| Tensile strength | Not specified | ≥200MPa (≥170MPa after immersion in water) | New key mechanical indicators |
Analysis of key technical requirements
4.1 Raw material specifications
The resin matrix must be unsaturated polyester resin (in accordance with GB/T 8237), and the reinforcement material is strictly limited to alkali-free glass fiber roving, with an alkali metal oxide content of ≤0.8%. High/medium alkali fibers produced in clay crucibles are prohibited.
4.4 Performance Index System
• Ring stiffness ≥50MPa (GB/T 5352 test)
• No structural damage after drop hammer impact (10kg/2m)
• No leakage after 0.1MPa water pressure sealing of joints for 15 minutes
Implementation Suggestions
Key Points of Quality Control
1. Raw Material Traceability: Establish a testing report system for alkali metal oxide content of glass fiber suppliers
2. Process Verification: The new BWFRP process must pass special tests for ring stiffness (Appendix A) and joint sealing
3. Dimensional control: Wall thickness deviation shall be in accordance with Table 3, and the positive deviation limit of SN100 grade conduit is +1.4mm
Standard connection instructions
Key specifications used in conjunction with this standard include:
• DL/T 802.1-2017 General technical requirements
• GB/T 5352-2008 Test method for axial properties of fiber reinforced plastic thermosetting plastic pipes

Loading PDF document...
Error loading PDF. Please make sure the file is valid and try again.
We also recommend
-

DL/T 2780-2024 in English
Guidelines for withstand voltage and synchronous partial discharge test of 110kV and above cross-linked polyethylene insulated AC submarine cables