GB/T 10963.3-2016 in English
SUPERSEDEDCircuit-breakers for overcurrent protection for household and similar installation―Part 3:Circuit-breakers for d.c.operation
- Issued on:2016-04-25
- Implemented on:2016-11-01
- File Format:PDF
- Delivery:Via email within 5 business days
$359.00
《GB/T 10963.3-2016家用及类似场所用过电流保护断路器 第3部分:用于直流的断路器》由TC189(全国低压电器标准化技术委员会)归口,TC189SC2(全国低压电器标准化技术委员会低压直流设备与应用分会)执行,主管部门为中国电器工业协会。
Introduction
Analysis of the core content of the standard
| Technical parameters | AC circuit breaker | DC circuit breaker (this standard) |
|---|---|---|
| Rated voltage | 220V/380V | Single-pole 250V/two-pole 500V |
| Time constant | Not applicable | T≤4ms or T≤15ms |
| Trip type | Type B/C | Type B/C/x (customizable) |
Key technical requirements
1. Structural characteristics
DC circuit breaker must meet the following requirements:
- Inter-pole linkage mechanism to ensure synchronous breaking (8.1.2)
- Minimum electrical clearance 4.0mm (pollution level 2 environment)
- Clearly mark the time constant T15 mark (6.k clause)
2. Key test items
Application guidance
Selection Recommendations
| Application scenarios | Recommended types |
|---|---|
| Photovoltaic system (<250V) | Single-pole B-type circuit breaker |
| Data center (440V) | Two-pole C-type circuit breaker (T15) |
Installation Precautions
Polarity identification (6.m clause) requirements:
Polarized circuit breakers must be marked with "+"/"-" terminals to prevent reverse connection and cause protection failure

Loading PDF document...
Error loading PDF. Please make sure the file is valid and try again.
We also recommend
-

GB/T 37751.33-2019 in English
Residual current operated circuit-breakers for household and similar use—Part 3-3: Specific requirements for RCDs with screw-type terminals for external untreated aluminium conductors and with aluminium screw-type terminals for use with copper or with aluminium conductors
2019-06-04 -

GB/T 40777-2021 in English
Requirements for automatic reclosing devices (ARDs) for circuit-breakers,RCBOs and RCCBs for household and similar uses
2021-10-11 -

GB/T 22200.5-2025 in English
Reliability of low-voltage apparatus—Part 5:Reliability test method of residual current operated circuit-breaker for household and similar uses
2025-12-31 -

GB/T 10963.1-2020 in English
Electrical accessories—Circuit-breakers for overcurrent protection for household and similar installations—Part 1: Circuit-breakers for a.c. operation
2020-11-19 -

GB/T 20640-2006 in English
Electrical accessories - Circuit-breakers and similar equipment for household use - Auxiliary contact units
2006-11-08 -

GB/T 24350-2009 in English
Selective circuit breakers for overcurrent protection for household and similar installation
2009-09-30 -

GB/T 37751.1-2019 in English
Residual current operated circuit-breakers for household and similar use—Part 1:Outline of blocks and modules for residual current devices standard
2019-06-04 -

GB/T 16916.21-2008 in English
Residual current operated circuit-breakers without integral overcurrent protection for household and similar uses (RCCB) - Part 21:Applicability of the general rules to RCCB functionally independent of line voltage
2008-06-19 -

GB 28527-2012 in English
Residual current devices with or without overcurrent protection for socket-outlets for household and similar uses
2012-06-29 -

GB/T 10963.3-2025 in English
Electrical accessories—Circuit-breakers for overcurrent protection for household and similar installations—Part 3: Circuit-breakers for DC operation
2025-10-31