GB/T 14598.2-2025 in English
VALIDMeasuring relays and protection equipment—Part 1: Common requirements
- Issued on:2025-05-30
- Implemented on:2025-05-30
- File Format:PDF
- Delivery:Via email within 8 business days
$582.00
| Standard No: | GB/T 14598.2-2025 |
| Document status: | VALID |
| Title in English: | Measuring relays and protection equipment—Part 1: Common requirements |
| Title in Chinese: | 量度继电器和保护装置 第1部分:通用要求 |
| Language: | English |
| File Format: | Electronic (PDF) |
| Delivery: | Via email within 8 business days |
| Issued on: | 2025-05-30 |
| Implemented on: | 2025-05-30 |
| Superseding: |
GB/T 14598.2-2011 Measuring relays and protection equipment—Part 1:Common requirements
|
| ICS Classification: | 29.120.70-Relays |
| Chinese Classification: | K45-Relay protection and automatic device |
| Professional Classification: | GB-National Standard |
| Related Keywords: | typeapplicable clausesspecial requirements digital protection device
protection equipment part following requirements common requirements introduction analysis content network security requirements |
| Related Topics: | Measuring relay +iec60255
|
《GB/T 14598.2-2025量度继电器和保护装置 第1部分:通用要求》由TC154(全国量度继电器和保护设备标准化技术委员会)归口,主管部门为中国电器工业协会。
Introduction
Analysis of the core content of the standard
Evolution of the standard and scope of application
This standard replaces GB/T 14598.2—2011 and is equivalent to the IEC 60255-1:2022 international standard. It is applicable to measuring relays and protection devices in power plants, substations and other scenarios, and covers the general technical requirements of distributed relay protection systems.
Major technical upgrades
| New content | Revised content | Deleted content |
|---|---|---|
|
|
|
Key parameter requirements
Environmental adaptability indicators
The equipment must meet the operating temperature range of -10℃~+55℃ (Table 1). Special environments require additional statements. According to the installation site, it is divided into 4 climate zones (Appendix B):
- Zone A: Control room (temperature controlled)
- Zone D: Outdoor without protection (withstands -40℃~+70℃)
Electromagnetic compatibility performance
According to the requirements of IEC 60255-26, all ports must meet the following requirements:
| Electrostatic discharge | ±8kV (contact discharge) |
| RF radiation | 10V/m (80MHz~1GHz) |
| Surge immunity | ±2kV (power line) |
Implementation points and suggestions
Design verification requirements
- Type testing needs to cover 12 major items (Table 12), including:
- Climate environment test (6.12)
- Seismic test (IEC 60255-21-3)
- Communication protocol consistency verification (6.6)
- Product family certification requires difference analysis (Clause 7.2)
Network security implementation
According to the requirements of Clause 6.7, a protection system should be established in combination with the following standards:
- IEC 62443-4-2 (Industrial Control System Security)
- IEEE 1686-2013 (Smart Device Cybersecurity)
- Communication ports need to declare encryption and authentication mechanisms
Typical application comparison table
| Equipment type | Applicable clauses | Special requirements |
|---|---|---|
| Digital protection device | 6.5, 6.7 | Must meet COMTRADE format (GB/T 14598.24) |
| Merging unit | 3.1.23, 6.5.1 | Synchronization accuracy must comply with IEC 61869-9 |