Sign In |Help & Support
ALL SECTORS
  • ALL SECTORS
  • GB(National Standard)
  • CB(Shipping)
  • CECS(Engineering Construction)
  • CJ(Urban Construction)
  • CY(News and Publication)
  • DB(Provincial Standard)
  • DL(Electricity & Power)
  • DZ(Geology & Mineralogy)
  • FZ(Spinning & Textile)
  • GA(Public Security)
  • HB(Aviation)
  • HG(Chemical Industry)
  • HJ(Environmental Protection)
  • JB(Machinery)
  • JC(Building Materials)
  • JG(Building & Construction)
  • JJ(Metering)
  • JT(Highway & Transportation)
  • LY(Forestry)
  • MT(Coal)
  • NB(Energy)
  • NY(Agriculture)
  • QB(Light Industry)
  • QC(Automobile & Vehicle)
  • QJ(Aerospace)
  • SH(Petrochemical)
  • SJ(Electronics)
  • SL(Water Resources)
  • SN(Commodity Inspection)
  • SY(Oil & Gas)
  • TB(Railway & Train)
  • YB(Ferrous Metallurgy)
  • YC(Tobacco)
  • YD(Telecommunication)
  • YY(Medical Device)
Database: 365,228(8 Aug 2026)
auxiliary power relay protection dedicated power supply protection system standard protection type key longitudinal differential protection typical protection narrow gauge mine car open type wheel assembly axles jb/t withstanding voltage testers scopethis type evaluation outline cest
GB/T 32576-2016 in English

GB/T 32576-2016 in English

VALID

Guide of calculating settings of auxiliary power relay protection for pumped storage power plant

  • Issued on:2016-04-25
  • Implemented on:2016-11-01
  • File Format:PDF
  • Delivery:Via email within 5 business days
Price(USD): $430.00
$418.00
Standard No: GB/T 32576-2016
Document status: VALID
Title in English: Guide of calculating settings of auxiliary power relay protection for pumped storage power plant
Title in Chinese: 抽水蓄能电站厂用电继电保护整定计算导则
Language: English
File Format: Electronic (PDF)
Delivery: Via email within 5 business days
Issued on: 2016-04-25
Implemented on: 2016-11-01
Professional Classification: GB-National Standard
Related Keywords: auxiliary power relay protection
dedicated power supply protection system
standard protection type key
longitudinal differential protection
typical protection
Related Topics: relay protection
Setting calculation
GBT32576
GB/T 32576-2016
Standardized design of relay protection
RO effluent conductivity calculation
Completion acceptance of pumped storage power station
Relay protection screen design
Acceptance of pumped storage power station
Relay protection service life
Environmental protection design of pumped storage power stations
Power plant coal station
Soil and Water Conservation Technology for Pumped Storage Power Station

《GB/T 32576-2016抽水蓄能电站厂用电继电保护整定计算导则》由524(中国电力企业联合会)归口,主管部门为中国电力企业联合会。


Introduction

Interpretation of the core content of the standard

Protection type Key setting parameters Sensitivity requirements Typical action time limit
High voltage plant transformer longitudinal differential protection Minimum action current (0.4-0.6) Ie
Slope 15%-30%
≥1.5 Instantaneous
Low voltage plant transformer overcurrent protection Self-starting coefficient Kst=5-7
Coordination coefficient 1.1-1.2
≥1.3 0.2-0.4s step difference
High voltage motor protection Quick-break high value (6-8)Ie
Low value (5-7)Ie
≥2.0 0s/0.3s

Key technical points

Short-circuit current calculation specification

The standard requires the use of GB/T 15544.1 and NB/T 35043 specifications:

  • Ignore the resistance component and use the sub-transient reactance Xd" saturation value
  • The equivalent electromotive force standard value is 1 and the phase is consistent
  • When calculating the periodic component, the non-periodic component coefficient Kap(1.5-2.0) needs to be considered

Typical protection setting case

Example of high-voltage plant transformer longitudinal differential protection:
A 6300kVA transformer, the measured unbalanced current is 0.15Ie:
  1. Minimum operating current = 1.3×(0.03×2+0.05)×Ie=0.143Ie→take 0.5Ie
  2. Slope S=(2.5-0.5)/(10-0.8)=0.22
  3. Differential quick break take 7Ie

Analysis of Standard Evolution

This standard establishes a dedicated power supply protection system for pumped storage for the first time. The innovations include:

  • Added special protection clauses for SFC transformers (Chapter 5.6)
  • Clarified the calculation method of motor feedback current (Formula 36)
  • Detailed the timing coordination of automatic switching of backup power supply (Article 5.7.3)

Implementation Suggestions

  1. New power stations should establish a setting calculation template according to Appendix A
  2. It is recommended to use the dynamic verification method to verify protection coordination
  3. Regularly test unbalanced current (Article 3.1 requirement)