GB/T 35466-2017 in English
VALIDDetermination of the emission of volatile organic compounds from wood-plastic composite for construction
- Issued on:2017-12-29
- Implemented on:2018-11-01
- File Format:PDF
- Delivery:Via email within 1~3 business days
$156.00
《GB/T 35466-2017建筑用木塑复合材料挥发性有机化合物(VOC)测定》由TC195(全国轻质与装饰装修建筑材料标准化技术委员会)归口,TC195SC2(全国轻质与装饰装修建筑材料标准化技术委员会木塑复合材料分会)执行,主管部门为中国建筑材料联合会。
Introduction
Interpretation of the core content of the standard
This standard specifies the method for determining volatile organic compounds in wood-plastic composite materials for construction using a small release chamber system, which is suitable for the detection of organic compounds with an initial boiling point ≤250℃.
Key Technical Requirements
| Parameters | Control Range | Accuracy Requirements |
|---|---|---|
| Temperature | 23-28℃ | ±0.5℃ |
| Relative Humidity | 50% | ±2% |
| Air Flow Rate | 0.5-1.5m/s | ±5% |
Test Process Detailed Explanation
Specimen preparation
The specimens need to be equilibrated for 15±2 days at 23±1℃ and 50±5%RH, with a spacing of ≥25mm to ensure air circulation. Hollow specimens need to be sealed with inert materials.
Sampling time nodes
- Key test points: 1 day (24h), 3 days (72h), 7 days (168h), 14±1 days, 28±2 days
- The test can be terminated early when the concentration is lower than the quantitative limit
Instrument configuration requirements
A small release chamber system that complies with GB/T 29899-2013 must be configured, and the following analytical equipment must be used:
- Thermal desorption-gas chromatography-mass spectrometry (GC-MS)
- Flame ionization detector (GC/FID)
- Sampling system with a flow range of 0-500mL/min
Implementation suggestions
Laboratory quality control
It is recommended to calibrate the standard curve weekly, and the deviation of the standard sample should be ≤15%. The sampling tube needs to be analyzed within 4 weeks.
Data Analysis Points
TVOC calculations must include all peaks from n-hexane to n-hexadecane, and qualitative and quantitative analysis must be performed on at least 10 main peaks.

Loading PDF document...
Error loading PDF. Please make sure the file is valid and try again.
We also recommend
-

GB/T 33499-2017 in English
The steel frame composite panels made from foamed cement
2017-03-03 -

GB/T 35462-2017 in English
Test method of mechanical fasteners in wood-plastic composites and products for construction
2017-12-29 -

GB/T 38107-2019 in English
Paving units for tactile sense approach
2019-10-18