Introduction
Analysis of the core content of the standard
This standard specifies the technical requirements for four types of grounding equipment for voltage source converter (VSC) flexible DC transmission systems:
- Connecting transformer neutral point grounding resistor: typical resistance 2000-15000Ω
- DC side grounding resistor: typical resistance 1000-6000kΩ
- Star-connected reactor grounding equipment: including linear/saturated reactor
- Grounding transformer equipment: ZN type or YNd type connection
Comparison of key technical indicators
| Equipment type | Resistance tolerance | Temperature limit (℃) | Key test items |
|---|---|---|---|
| Neutral point grounding resistor | ±5% | 250-650 | Temperature rise test, impulse current test |
| DC side grounding resistor | ±5% | 250-650 | DC withstand voltage test (2 times rated voltage) |
| Star-connected reactor | - | According to GB/T1094 | Zero-sequence impedance measurement |
| Grounding transformer | - | According to GB/T1094 | Short-circuit withstand capacity test |
Typical application scenario analysis
Modular multilevel converter (MMC) system
In the ±500kV Zhangbei flexible DC power grid project, the star-connected reactor grounding equipment is used to achieve:
- Suppress DC bias current (typical value ≤3%A)
- Withstand short-circuit current of 20kA/100ms in case of fault
- Zero-sequence reactance is controlled in the range of 5-10Ω
Standard Evolution and Innovation
This standard systematically solves the three major technical problems of VSC-HVDC grounding equipment for the first time:
- Magnetic saturation problem of reactor caused by DC bias current
- Resistor inductance control under high frequency conditions (requirement L<0.02R/2πfh)
- Stability of composite insulation materials at high temperatures of 450-650℃
Engineering Implementation Recommendations
Key Points for Selection and Design
| Parameters | Calculation formula | Example value |
|---|---|---|
| Hot resistance value | Rhot=R25/(1-α25×Δθ) | 5500Ω(+8%) |
| Equivalent test current | It=√(P/R), P=W/t1 | 1200A/3s |
Insulation and operation requirements
- When the altitude is>1000m, the insulation level must be corrected according to GB/T311.1
- In areas with pollution level ≥d, the casing anti-pollution design should be strengthened
- The resistance deviation between resistor units is ≤1%

Loading PDF document...
Error loading PDF. Please make sure the file is valid and try again.
We also recommend
-

GB/Z 25320.1001-2023 in English
Power systems management and associated information exchange— Data and communication security—Part 100-1 : Conformance test cases for IEC 62351-5 and IEC TS 60870-5-7
2023-12-28 -

GB/T 44773-2024 in English
Technical specifications for remote automatic power control (ADC) of high voltage direct current converter station
2024-10-26 -

GB/T 38318-2019 in English
Cyber security assessment guide for electric power system supervision and control
2019-12-10 -

GB/T 25320.11-2023 in English
Power systems management and associated information exchange—Data and communications security—Part 11:Security for XML documents
2023-12-28 -

GB/T 31460-2015 in English
Technical guide for reactive power compensation and allocation of HVDC converter stations
2015-05-15 -

GB/T 42151.92-2025 in English
Communication networks and systems for power utility automation—Part 9-2: Specific communication service mapping(SCSM)—Sampled values over ISO/IEC 8802-3
2025-10-31 -

GB/T 34930-2017 in English
Operation and control specification for microgrids connected to distribution network
2017-11-01