TB/T 2993.1-2016 in English
VALIDRailway communication power supply. Part 1: General requirements of power supply system for communication
- Issued on:2016-11-18
- Implemented on:2017-06-01
- File Format:PDF
- Delivery:Via email within 1~3 business days
$117.00
| Standard No: | TB/T 2993.1-2016 |
| Document status: | VALID |
| Title in English: | Railway communication power supply. Part 1: General requirements of power supply system for communication |
| Title in Chinese: | 铁路通信电源 第1部分:通信电源系统总技术要求 |
| Language: | English |
| File Format: | Electronic (PDF) |
| Delivery: | Via email within 1~3 business days |
| Issued on: | 2016-11-18 |
| Implemented on: | 2017-06-01 |
| Professional Classification: | TB-Railway Transport |
| Related Keywords: | railway communication power supply
communication power supply system power supply system power supply monitoring system railway communication power supply series standards |
| Related Topics: | tb/t 1961-2016
tb/t3441-2016 tb/t3367-2016 tb/t2993.5-2016 Power Systems power always cut off Communication circuit board gold source tb/t3440-2016 Communication power Lightning Protection Technology of Communication Engineering Power System power supply tb/t 3466-2016 tb/t 3432-2016 |
Introduction
Interpretation of the core content of the standard
TB/T 2993.1-2016, as the basic part of the railway communication power supply series standards, systematically stipulates the technical requirements of key components such as high-frequency switching rectifier equipment and UPS system. For the first time, the standard clearly subdivides the communication power supply system into 6 subsystems, reflecting the modular design concept of railway communication power supply.
System Architecture and Technical Parameters
| Subsystem | Key Indicators | Allowable Range |
|---|---|---|
| External AC Power Supply | Voltage Fluctuation | -20%~+20% |
| DC Power Supply System | Output Voltage | -43.2V~-57.6V |
| UPS Equipment | MTBF | ≥5×10⁴h(Indoor Type) |
Analysis of key technical requirements
Power supply reliability guarantee
The standard requires that dual-channel AC input must be equipped with electrical + mechanical double interlocking devices, and the MTBF index must reach more than 1×10⁴ hours. In particular, the strict requirements for the noise voltage of high-frequency switching rectifier equipment are proposed in reference to TB/T 2993.2-2016.
UPS working mode
- Parallel redundant mode: multiple UPSs can be connected in parallel through a synchronous controller
- Independent dual bus: two completely independent power supply systems
- Stand-alone mode requires a backup battery pack
Implementation suggestions
Lightning protection and grounding system construction
Article 9.2 of the standard clearly requires the use of voltage-limiting SPD devices. It is recommended to install a Class I SPD at the input end of the distribution cabinet, and its voltage protection level Up should be ≤2.5kV. Typical implementation plan:
- AC power distribution panel is equipped with three-level SPD protection
- DC working grounding resistance ≤4Ω
- Equipment rack and grounding bus are connected by 35mm² copper cable
Standard evolution analysis
Compared with the old version of the standard, the 2016 version is mainly improved in the following aspects:
- New outdoor MTBF requirements for UPS equipment (≥1×10⁴h)
- Clearly define the quantitative indicator of DC power supply voltage drop ≤3.2V
- Strengthen the interface specification between power supply monitoring system and railway environmental monitoring

Loading PDF document...
Error loading PDF. Please make sure the file is valid and try again.
We also recommend
-

TB/T 2872-1998 in English
Test method for compatibility of filter element materials and fluids for diesel locomotives
1998-02-24 -

TB/T 1759-2016 in English
Rules for installation of cabling for railway passenger car
2016-09-30 -

TB/T 2874-1998 in English
Test method for rated end load of diesel locomotive filter elements
1998-02-24 -

TB/T 3166-2016 in English
Stand test methods of diesel locomotives traction and thermodynamic performance
2016-05-26 -

TB/T 2873-1998 in English
Test method for anti-collapse and anti-crack performance of diesel locomotive filter elements
1998-02-24