XF/T 3012-2020 in English
VALIDFireproof board for steel structure
- Issued on:2020-11-10
- Implemented on:2021-05-01
- File Format:PDF
- Delivery:Via email within 5 business days
$311.00
| Standard No: | XF/T 3012-2020 |
| Document status: | VALID |
| Title in English: | Fireproof board for steel structure |
| Title in Chinese: | 钢结构防火保护板 |
| Language: | English |
| File Format: | Electronic (PDF) |
| Delivery: | Via email within 5 business days |
| Issued on: | 2020-11-10 |
| Implemented on: | 2021-05-01 |
| ICS Classification: | 13.220.50-Fire-resistance of building materials and elements |
| Chinese Classification: | C84-Fire-fighting equipment and devices |
| Related Topics: | xf
Steel structure version steel structure Environmental protection tank instrument structure Nandi Structural Plate /xf xf/ Fire resistance of steel structures steel structure fire protection Steel structure connecting plate protective steel plate Steel structure construction safety protection fire protection Moisture deformation rate Shield'' Fireproof board country Structural adhesive maintenance standards EU steel structure fire protection xf/t 537 |
本文件规定了钢结构防火保护板的定义及分类、技术要求、试验方法、检验规则、综合判定准则和包装、标志、标签、贮运、产品说明书等内容。
本文件适用于建(构)筑物工程钢结构表面使用的各类钢结构防火保护板。
Introduction
Interpretation of the core content of the standard
| Technical dimensions | Ordinary building boards | Special building boards |
|---|---|---|
| Fire resistance classification | 0.5-3.0 hours (building fiber) | 0.5-3.0 hours (HC hydrocarbons) |
| Environmental tolerance | Basic weathering requirements | Acid/alkali/salt spray/freeze-thaw cycle resistance |
| Combustion performance | FIGRA≤250W/s | Additional high temperature impact test |
Detailed explanation of key technical indicators
Fire resistance test: The standard stipulates that HN400×200 steel (section coefficient 161m-1) and 36b I-steel (126m-1) are used as the base material, and four-point loading is used to simulate the actual stress state. The judgment conditions include:
- Bearing capacity: deformation ≤L/20 (L is the clear span)
- Temperature control: average temperature ≤538℃
Implementation suggestions
Selection guide:Petrochemical projects should choose TS composite panels (such as HCGB-TS Fac2.00-F22), whose chemical corrosion resistance is verified by a 30-day salt spray test. High-rise buildings are recommended to use PT D-type panels (such as HCGBE-PT Fxn1.50-D16), with a surface density of ≤25kg/m2.
Installation points:The standard emphasizes that the 150mm lightweight concrete cover should be used in conjunction with aluminum silicate fiber wool for cladding construction, and the maintenance environment should be controlled at 5-35℃/50-80%RH.
Analysis of Standard Evolution
Main upgrades compared to the old version:
- Added applicable scenarios for HC hydrocarbon fire curves
- Clarified test exemption clauses for composite board decorative surface layers
- Introduced refined indicators such as edge straightness (≤0.3‰)

Loading PDF document...