DL/T 368-2024 in English
VALIDHigh-altitude correction for insulator external insulation in pollution-prone overhead power lines
- Issued on:2024-12-25
- Implemented on:2025-06-25
- File Format:PDF
- Delivery:Via email within 1~3 business days
$184.00
| Standard No: | DL/T 368-2024 |
| Document status: | VALID |
| Title in English: | High-altitude correction for insulator external insulation in pollution-prone overhead power lines |
| Title in Chinese: | 输电线路用绝缘子污秽外绝缘的高海拔修正 |
| Language: | English |
| File Format: | Electronic (PDF) |
| Delivery: | Via email within 1~3 business days |
| Issued on: | 2024-12-25 |
| Implemented on: | 2025-06-25 |
| ICS Classification: | 29.080.10-Insulators |
| Chinese Classification: | K48-Insulator |
| Professional Classification: | DL-Electricity |
| Related Keywords: | altitude correction system
high-altitude correction correction basis altitude edition altitude correction formula χ=1/ [ altitude correction factor χ |
Introduction
Analysis of the core content of the standard
The new version of DL/T368-2024 establishes an altitude correction system based on the unified creepage distance (USCD) to address the problem of contaminated external insulation of insulators in high-altitude areas. Compared with the 2010 edition, the main technical innovations are reflected in:
| Technical elements | 2010 edition | 2024 edition |
|---|---|---|
| Altitude correction formula | χ=1/[1-0.12n(H-1)] | Optimize the symbol system, clarify the χH/χsl relationship |
| n value selection | Fixed value (AC 0.55/DC 0.40) | Range value (AC 0.50-0.60/DC 0.35-0.45) |
| Correction basis | Altitude only | Dual track system (altitude or air pressure data) |
Key technical parameter description
The calculation of the altitude correction factor χ adopts the dual track method:
- Based on altitude: χ=1/[1-0.12n(H-1)] (H unit: km)
- Based on air pressure data: χ=(PH/P1)-n (P1=89.8kPa)
Engineering Application Example
A ±800kV DC line passes through an area with an altitude of 3500m. When composite insulators are selected:
- Take n=0.40 (DC recommended value)
- Calculated χ=1/[1-0.12×0.40×(3.5-1)]=1.14
- That is, USCD needs to be increased by 14%
Standard Implementation Recommendations
Design Phase
- Pressure data correction method is preferred (higher accuracy)
- For new projects, the n value is strictly selected according to the range in Table 1
Operation and Maintenance Phase
- Regions below 1000m above sea level should directly refer to GB/T26218 series standards
- Regularly check the deviation between the actual air pressure on site and the standard value
Special working condition processing
For substation post insulators, it is recommended to add a safety margin of 5%-10% based on the standard calculation results.