DL/T 1999-2019 in English
VALIDMethod of on-site DC partial discharge test for converter transformer
- Issued on:2019-06-04
- Implemented on:2019-10-01
- File Format:PDF
- Delivery:Via email within 1~3 business days
$185.00
Introduction
Analysis of the core content of the standard
This standard establishes a technical system for on-site testing of DC partial discharge of converter transformers for the first time, focusing on solving the following key problems:
- Differences in DC discharge characteristics: Compared with AC partial discharge, DC partial discharge pulses are characterized by strong randomness and low repetition rate (about 3 orders of magnitude lower)
- On-site interference control: It stipulates the identification methods and suppression measures of 6 types of interference sources, including special problems such as corona discharge and spatial interference
- Test severity: It is required to directly boost the voltage to the test voltage (pre-pressurization is not allowed), and 800kV equipment must be tested for 90 minutes
Comparison of key technical parameters
| Voltage level | Grading ring diameter (mm) | Standing time (h) | 96 | Factory value 85% |
|---|---|---|---|
| 500kV | 600 | 72 | Factory value 85% |
| 800kV | 1600 | 96 | Factory value 85% |
Typical application case
±500kV converter transformer, after the differential signal method in Appendix B was used:
- Spatial interference was reduced from 1500pC to 300pC
- Corona discharge of the valve side bushing grading ring was effectively identified (UV imaging confirmation)
- The test was passed after replacing the 800mm diameter grading ring
Implementation suggestions
- Equipment selection: The ripple factor of the DC generator must be <3%, and the partial discharge instrument must have the function of pulse polarity identification
- Environmental control: The test should be suspended when the relative humidity is >80%, and the oil temperature should be maintained in the range of 10-30℃
- Safety protection: During the 800kV test, the angle between the high-voltage lead and the ground is ≥60°, and the surface field strength of the grading ring is ≤13kV/cm
- Data interpretation: Pay attention to distinguishing between effective discharge pulses (opposite polarity) and external interference (same polarity)

Loading PDF document...
Error loading PDF. Please make sure the file is valid and try again.
We also recommend
-

DL/T 790.12-2001 in English
Distribution Automation Using Distribution Line Carrier Part 1: General Provisions Part 2: Guidelines for Formulation of Specifications
2001-12-26 -

DL/T 790.11-2001 in English
Distribution Automation Using Distribution Line Carriers Part 1: General Part 1: Architecture of Distribution Automation Systems
2001-12-26 -

DL/T 581-2021 in English
Condenser tube rubber ball cleaning equipment and cooling water debris filter
2021-12-22 -

DL/T 846.3-2017 in English
General technical specifications for high voltage test equipments Part 3:high voltage switch integrate detector
2017-12-27